Author:Hajanti, Petteri
Title:Palvelinkeskuksen jäähdytysjärjestelmän teknis-taloudellinen optimointi
Technological and economical optimization of data center cooling system
Publication type:Master's thesis
Publication year:2013
Pages:(12) + 125      Language:   fin
Department/School:Energiatekniikan laitos
Main subject:LVI-tekniikka   (Ene-58)
Supervisor:Sirén, Kai
Instructor:Laine, Tuomas ; Jaatinen, Jukka ; Innanen, Jari
OEVS:
Electronic archive copy is available via Aalto Thesis Database.
Instructions

Reading digital theses in the closed network of the Aalto University Harald Herlin Learning Centre

In the closed network of Learning Centre you can read digital and digitized theses not available in the open network.

The Learning Centre contact details and opening hours: https://learningcentre.aalto.fi/en/harald-herlin-learning-centre/

You can read theses on the Learning Centre customer computers, which are available on all floors.

Logging on to the customer computers

  • Aalto University staff members log on to the customer computer using the Aalto username and password.
  • Other customers log on using a shared username and password.

Opening a thesis

  • On the desktop of the customer computers, you will find an icon titled:

    Aalto Thesis Database

  • Click on the icon to search for and open the thesis you are looking for from Aaltodoc database. You can find the thesis file by clicking the link on the OEV or OEVS field.

Reading the thesis

  • You can either print the thesis or read it on the customer computer screen.
  • You cannot save the thesis file on a flash drive or email it.
  • You cannot copy text or images from the file.
  • You cannot edit the file.

Printing the thesis

  • You can print the thesis for your personal study or research use.
  • Aalto University students and staff members may print black-and-white prints on the PrintingPoint devices when using the computer with personal Aalto username and password. Color printing is possible using the printer u90203-psc3, which is located near the customer service. Color printing is subject to a charge to Aalto University students and staff members.
  • Other customers can use the printer u90203-psc3. All printing is subject to a charge to non-University members.
Location:P1 Ark Aalto  5718   | Archive
Keywords:data center
cooling system
optimization
free cooling'
energy efficiency
life cycle costs
palvelinkeskus
jäähdytysjärjestelmä
optimointi
vapaajäähdytys
energiatehokkuus
Abstract (eng): This master's thesis studies data center cooling.
The aim of this thesis is to discover the most energy efficient and cost effective cooling solutions for data centers.
In addition, the optimal air temperature for data centers, profitability of heat recovery and the influence of geographical location on data center energy consumption are investigated.

The results shown in this thesis are based on computational examinations that are executed by self-made computer program.
Computer program is capable of accomplishing energy simulation tasks and optimization problems with several variables.
The optimization variables are the temperatures of cold aisle, chilled water supply and the liquid (water ethylene glycol) used for free cooling as well as the size of free cooling plate heat exchanger and the count of computer room air handling (CRAH) units.
Optimization allowed the discovering of energy efficient and cost effective cooling solutions.

The results show, that chiller-less sea water cooling is the most energy efficient and cost effective cooling solution studied in this thesis.
However, the chiller and refrigeration based cooling systems can also be very energy efficient if the system is optimized and the cooling system temperatures are allowed to change dynamically.
The results show, that in Finland, dynamical chiller based cooling systems can utilize free cooling over 80 % of time.
Optimization significantly decreased the energy consumption of the cooling systems compared to the standard non-optimized design.

The cold aisle temperature has an energy impact on both, the performance of the cooling system and IT equipment.
The optimal temperature range can be found where the combined IT load and cooling system energy consumption is minimized.
The results show, that in stationary cases and in cold climates the optimal cold aisle temperature is only 20 23°C.
Hot aisle temperature is at least important as the cold aisle temperature.
Hot aisle containment system enables the design of highly energy efficient cooling systems.
The influence of geographical location on data center energy consumption is significant if the cooling system can utilize free cooling.
If the cooling system can't utilize free cooling the influence of geographical location is less significant.
Abstract (fin): Tässä opinnäytetyössä tutkitaan palvelinkeskuksen jäähdytystä.
Tutkimuksen ensisijaisena tavoitteena on löytää annetuista järjestelmävaihtoehdoista teknis-taloudellisesti paras tapa tuottaa palvelinkeskuksen jäähdytykseen tarvittava kylmäenergia.
Lisäksi tutkitaan jäähdytysilman (kylmäkäytävä) optimaalista lämpötilaa, lämmöntaiteenoton kannattavuutta sekä maantieteellisen sijainnin vaikutusta palvelinkeskuksen energiankulutukseen.

Opinnäytetyössä esitetyt tutkimustulokset perustuvat laskennallisiin tarkasteluihin, jotka on tehty itse koodatun tietokoneohjelman avulla.
Tietokoneohjelmassa yhdistyvät energiasimulointi ja optimointi.
Optimoinnin päätösmuuttujina ovat jäähdytysilman, jäähdytysveden sekä vapaajäähdytystilanteessa nestejäähdyttimeltä lähtevän liuoksen lämpötilat.
Näiden lisäksi optimoidaan vapaajäähdytyksessä käytettävän levylämmönsiirtimen kokoa sekä vakioilmastointikoneiden lukumäärää.
Optimointi mahdollisti energia- ja kustannustehokkaiden ratkaisujen löytymisen.

Saatujen tulosten perusteella merivesijäähdytys on tässä tutkimuksessa vertailluista vaihtoehdoista energia- ja kustannustehokkain tapa toteuttaa suuren palvelinkeskuksen jäähdytys.
Myös vapaajäähdytystä hyödyntävät vedenjäähdytyskoneistot voivat olla hyvin energiatehokkaita, jos niiden toiminta on optimoitu ja järjestelmän lämpötilojen sallitaan muuttuvan dynaamisesti.
Opinnäytetyössä saatujen tulosten perusteella dynaamisesti toimivat jäähdytysjärjestelmät voivat hyödyntää vapaajäähdytystä parhaimmillaan jopa yli 80 % vuoden tunneista.
Optimointi vähensi huomattavasti kaikkien vertailuun osallistuneiden jäähdytysjärjestelmien energiankulutusta verrattuna järjestelmäkohtaiseen perusratkaisuun.

Jos jäähdytysilman lämpötilaa halutaan nostaa, tulee aina huomioida toimenpiteen vaikutus myös palvelimien ja vakioilmastointikoneiden energiankulutukseen.
Jos jäähdytysjärjestelmä toimii stationäärisillä lämpötiloilla, kylmäkäytävän optimaalinen lämpötila on välillä 20 - 23 °C.
Kuumakäytävän lämpötilalla on vähintään yhtä suuri merkitys jäähdytysjärjestelmän energiatehokkuuteen kuin kylmäkäytävän lämpötilalla.
Kuumakäytävän osastoiminen omaksi kammiokseen (Hot Aisle Containment System) luo hyviin perustan huippuenergiatehokkaan jäähdytysjärjestelmän suunnittelulle.
Maantieteellisen sijainnin vaikutus jäähdytysjärjestelmän energiankulutukseen on hyvin merkittävä vapaajäähdytystä hyödyntävillä järjestelmillä.
Jos jäähdytysjärjestelmä ei pysty hyödyntämään vapaajäähdytystä, on sijainnin vaikutus huomattavasti merkityksettömämpi.