search query: @keyword substation / total: 11
reference: 1 / 11
« previous | next »
Author:Nepola, Kimmo
Title:Radiotaajuisten osittaispurkausmittausten soveltuvuus suurjännitteisten sähköasemalaitteiden kunnonvalvontaan
Feasibility of radio frequency interference measurements in condition monitoring of high voltage substations
Publication type:Master's thesis
Publication year:2013
Pages:71 s. + liitt. 6      Language:   fin
Department/School:Sähkötekniikan laitos
Main subject:Sähköjärjestelmät   (S3015)
Supervisor:Haarla, Liisa
Instructor:Kuosa, Daniel
Electronic version URL: http://urn.fi/URN:NBN:fi:aalto-201307127184
OEVS:
Electronic archive copy is available via Aalto Thesis Database.
Instructions

Reading digital theses in the closed network of the Aalto University Harald Herlin Learning Centre

In the closed network of Learning Centre you can read digital and digitized theses not available in the open network.

The Learning Centre contact details and opening hours: https://learningcentre.aalto.fi/en/harald-herlin-learning-centre/

You can read theses on the Learning Centre customer computers, which are available on all floors.

Logging on to the customer computers

  • Aalto University staff members log on to the customer computer using the Aalto username and password.
  • Other customers log on using a shared username and password.

Opening a thesis

  • On the desktop of the customer computers, you will find an icon titled:

    Aalto Thesis Database

  • Click on the icon to search for and open the thesis you are looking for from Aaltodoc database. You can find the thesis file by clicking the link on the OEV or OEVS field.

Reading the thesis

  • You can either print the thesis or read it on the customer computer screen.
  • You cannot save the thesis file on a flash drive or email it.
  • You cannot copy text or images from the file.
  • You cannot edit the file.

Printing the thesis

  • You can print the thesis for your personal study or research use.
  • Aalto University students and staff members may print black-and-white prints on the PrintingPoint devices when using the computer with personal Aalto username and password. Color printing is possible using the printer u90203-psc3, which is located near the customer service. Color printing is subject to a charge to Aalto University students and staff members.
  • Other customers can use the printer u90203-psc3. All printing is subject to a charge to non-University members.
Location:P1 Ark Aalto  1201   | Archive
Keywords:partial discharge
substation
radio frequency interference
condition monitoring
osittaispurkaus
sähköasema
radiotaajuinen osittaispurkausmittaus
kunnonvalvonta
Abstract (eng):Partial discharges resulting from strong and inhomogeneous electrical fields are one of the major factors which accelerate the degeneration of electrical insulations.
Partial discharge monitoring provides early warnings for upcoming failures and thereby allows for scheduling of maintenance actions before a complete breakdown.

This thesis assesses the feasibility of radio frequency measurements used in condition monitoring of high voltage substations.
Detection of internal discharges in power and instrument transformers, bushings and cable terminations are of particular interest.
The RFI method is evaluated based on laboratory measurements and measurements performed at 13 high voltage substations along with practical experience and prior research.
The economical perspective is not addressed in this thesis.

Based on the results presented in this thesis, it is possible to detect and locate partial discharges at high voltage substations.
Using an omnidirectional antenna and signal attenuation, partial discharge can typically be located within the accuracy of a device cluster in a switch bay.
Incorporating frequency spectrum information produced by varying partial discharges with the suspected signal source (fault location) enables evaluation of partial discharge type.
RFI measurements allow for the screening of large populations as they can be performed without unnecessary service interruptions.
The magnitude or severity of partial discharges cannot be evaluated with the RFI method.
However, other more accurate diagnostic measurements can be targeted to confirm partial discharge once they are initially discovered using the RFI method.

As a conclusion, RFI measurements are feasible for condition monitoring of high voltage substations.
However in addition, operational reliability, economic feasibility, and personal safety aspects are to be evaluated before implementing this method.
Abstract (fin):Suurjännitteisten sähköasemalaitteiden eristysrakenteissa kehittyviin vikoihin liittyy usein voimakkaassa ja epähomogeenisessa sähkökentässä syntyviä osittaispurkauksia.
Osittaispurkausmittausten avulla on mahdollista saada varoitus kehittyvästä viasta ja siten ajoittaa huoltotoimenpiteet ennen kuin laitteen täydellinen tuhoutuminen ja siitä verkolle aiheutuva häiriö ehtivät tapahtua.

Tämän tutkimuksen tavoitteena oli selvittää, soveltuvatko radiotaajuiset osittaispurkausmittaukset (RFI-mittaukset) suurjännitelaitteiden kunnonvalvontaan.
Erityisen mielenkiinnon kohteena oli muuntajissa, mittamuuntajissa, läpivienneissä ja kaapelipäätteissä esiintyvien sisäisten osittaispurkauksien havaitseminen.
Tässä työssä toteutettu RFI-menetelmän arviointi perustuu 13:lla kantaverkon sähköasemalla tehtyihin mittauksiin ja niiden vertailuun suurjännitelaboratoriossa suoritettuihin referenssimittauksiin, mittauksista saatuihin käytännön kokemuksiin sekä aiempaan tutkimustietoon aiheesta.
Menetelmän soveltuvuutta ei arvioitu taloudellisesta näkökulmasta.

Diplomityössä tehtyjen mittausten perusteella todetaan, että menetelmällä pystytään havaitsemaan ja paikantamaan sähköasemalaitteissa esiintyviä osittaispurkauksia.
Vikapaikka pystytään pääsääntöisesti löytämään laiteklusterin tarkkuudella, kun käytettään ympärisäteilevää antennia ja hyödynnetään signaalin voimistumista vikapaikkaa lähestyttäessä.
Yhdistelemällä tietoa eri osittaispurkausten synnyttämistä taajuusspektreistä epäiltyyn vikapaikkaan pystytään tekemään arvioita osittaispurkauksen tyypistä.
Menetelmällä pystytään seulomaan suuria laitepopulaatioita, koska mittaukset voidaan tehdä ilman käyttökeskeytyksiä.
RFI-mittausten perusteella ei voida suoraan arvioida purkausvian suuruutta tai vakavuutta.
Epäillylle vikakohteelle voidaan kuitenkin kohdistaa muita tarkentavia diagnostisia mittauksia, jotka vahvistavat osittaispurkaushavainnon ja vian vakavuuden.

Johtopäätöksissä todetaan RFI-menetelmän soveltuvan suurjännitteisten sähkö-asemalaitteiden kunnonvalvontaan.
Menetelmän käyttöönottoa on kuitenkin arvioitava myös käyttövarmuuden, henkilöturvallisuuden ja taloudellisista näkökulmista.
ED:2013-12-02
INSSI record number: 48030
+ add basket
« previous | next »
INSSI